- the device includes 4 switchable contacts which are triggered in case of rain/wind, or at mains supply failure; the contact remains switched for a preset time after the ending of rain fall/wind,
- alarm triggering rain intensity is preset by the user (minor rainfall - intense rainfall),
- alarm triggering wind force value is preset by the user, ranging from weak wind (about 5 m/s) to strong wind (about 15 m/s),
- additional input for flap opening sensor (closed when open), allows for optical monitoring of the flaps status,
- the device includes indication of the following states:
- 230 V~ supply - green LED,
- "wind" alarm - red LED,
- "rain" alarm - red LED,
- "flap open" indication - yellow LED,
- wind speed indication - light scale: 7 yellow and 1 red LED (red for wind speed above 15 m/s).
Dimensions:
180 x 180 x 75 mm
Additional accessories:
KE 2a expansion module
Controlling contactor for expansion of mcr P054 weather control unit to over four independent control groups that are simultaneously shut during wind or rain.
- 230 V~ control voltage, 5A/ 230 V~ voltage-free contact,
- thermoplastic casing, grey RAL 7035,
- dimensions: 158 x 118 x 76 [mm] (width x height x depth).
- controlling contactor with six contacts for expanding the weather control unit to five independent groups.