Fire resistance class EI120 (ve ho o→i)S / EI120 (ve i→o) / EI180 (ve o→i)S. The valves are certified for conformity with EN 15650, classified pursuant to EN 13501-3, and tested according to EN 1366-2.
mcr DOR smoke dampers are intended for installation in automatically operated fire ventilation systems. The devices are used in fire ventilation systems. The dampers prevent fire, smoke and fire gases from spreading to the adjacent zones. During normal system operation, the damper blade is closed. The fire damper blade in the fire compartment is opened, whereas in other areas the blades are closed. Admissible flow velocity in the connected duct is 15 m/s.
mcr WIP LD dampers consist of a casing with a rectangular cross-section, multiple moving damper blades – louvers rotating around their own axes – and a remotely activated trigger and control mechanism, which is installed inside the damper clearance.
Our mcr FID WING fire dampers are designed for installation at penetrations of day-to-day ventilation ductwork through the building walls and horizontal assemblies
This site uses the cookies to ensure better user experience and functionality. Using our site you agree to using cookies. Cookies can be allowed or blocked, or adjusted. Check it.
(+48) 58 341 42 45
ul. Grzegorza z Sanoka 2
80-408 Gdańsk
Mercor © 2024 All rights reserved.
Projekt i wykonanie:Wiselimber Interactive